目次へ 【独立基礎_Cbタイプ】 |
|
|
|
|
|
|
|
設備耐震_独立基礎_Cb |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
●基礎の浮き上がりの検討 |
|
|
|
|
|
|
|
|
|
|
(1-Kv)[(Lg+(Lf-L)/2*W+Lf*Wf/2]>Kh[(hf+hg)*W+hf*Wf/2] |
|
|
|
|
|
|
|
(1-0.5)[(50+(150-100)/2)*1.9+150*85E-01/2]=39E+01>1[(35+90)*1.9+35*8.5/2]=39E+01 |
|
1 |
|
|
●判定
OK |
|
|
|
|
|
|
|
|
|
|
|
ここで、 |
L=設備機器のボルトスパン=100[cm] |
|
|
|
|
100 |
|
Lg=設備機器の重心位置=50[cm] |
|
|
|
|
50 |
|
hg=設備機器重心高さ=90[cm] |
|
|
|
|
90 |
|
Lf=基礎長さ=150[cm] |
|
|
|
|
|
150 |
|
hf=基礎高さ=35[cm] |
|
|
|
|
|
35 |
|
Bf=基礎幅=35cm] |
|
|
|
|
|
35 |
|
Kh=設計用水平震度=1 |
|
|
|
|
1 |
|
Kv=設計用鉛直震度=0.5 |
|
|
|
|
|
|
W=設備機器重量=1.9[kN] |
|
|
|
|
1.9 |
|
Wf=基礎重量 |
|
|
|
|
|
|
|
=hf*Lf*Bf*γ*z=35*150*35*23E-06*2=8.5[kN] |
|
|
|
|
|
γ=コンクリート比重量=23E-06[kN/cm3] |
|
|
|
23 |
|
z=基礎個数=2 |
|
|
|
|
|
2 |
|
|
|
|
|
|
|
|
|
●断面寸法の制限 |
|
|
|
|
|
|
|
Bf=35≧30[cm] |
|
|
|
|
|
|
|
|
|
|
|
hf/Bf=1≦1 |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
ここで、 |
hf=基礎高さ=35[cm] |
|
|
|
|
|
|
|
|
|
20 |
|
Bf=基礎幅=35[cm] |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|